DulyTrack
Reserve

How Often Must an Aerobic System Be Inspected in Texas?

Last verified Oct 5, 2026

A Texas aerobic treatment system must be tested and inspected at least once every four months, which is three visits per year. The requirement is in 30 TAC §285.91(4), Table IV, which sets the testing frequency for “Any Treatment Method in Conjunction with Surface Application” and “Any Secondary Treatment System” at “At least once every four months.”

The frequency can be reduced to two tests per year under 30 TAC §285.7(e)(3) when the system has “electronic monitoring and automatic telephone or radio access that will notify the maintenance provider of system or components failure and will monitor the amount of disinfection in the system.” The provider must keep that monitoring working.

Each visit includes the component inspection in Figure 3 (30 TAC §285.90(3)), the Table IV tests, marking the tag (§285.7(e)(2)), and a report to the permitting authority and owner within 14 days (§285.7(e)(1)(B)). Local authorities may require more.

Summarizes public rules as of Oct 5, 2026; not legal advice; verify with your permitting authority.

Where does the four-month rule come from?

Two sections work together. 30 TAC §285.7(e)(1) says the maintenance provider “shall test and report for each system as required in §285.91(12) of this title.” Table XII in §285.91(12) identifies which system types need testing and reporting, and footnote (2) of that table sends you to §285.91(4) for the frequency. Table IV then sets the schedule.

Type and size of treatment unit (Table IV)Testing frequencyRequired testsMinimum acceptable result
Any treatment method with surface applicationAt least once every four monthsTotal chlorine residual or fecal coliform at each required test; one BOD5 and TSS grab sample per year (non-single-family only)0.1 mg/l residual in pump tank, or fecal coliform not to exceed 200 MPN/100 ml; BOD5 and TSS not to exceed 65 mg/l
Any secondary treatment systemAt least once every four monthsNoneNone
Non-standardPermit specificPermit specificPermit specific

Source: 30 TAC §285.91(4), Table IV.

Two things stand out in the table. The four-month interval applies to both surface-application systems and secondary treatment systems with subsurface disposal (drip, drainfield, mound, and so on). The difference is what you test: surface-application systems carry a chlorine residual or fecal coliform test; secondary treatment systems with subsurface disposal have no required laboratory or field test, but the visit, the component inspection, and the report still happen.

When can a system drop to two visits a year?

30 TAC §285.7(e)(3):

“The number of required tests may be reduced to two per year for all systems having electronic monitoring and automatic telephone or radio access that will notify the maintenance provider of system or components failure and will monitor the amount of disinfection in the system. The maintenance provider shall be responsible for ensuring that the electronic monitoring and automatic telephone or radio access systems are working properly.”

To qualify, the monitoring has to do two jobs: notify the provider of a system or component failure, and monitor the disinfection level. An alarm light by itself does not meet that text. The rule says the number of tests “may be reduced,” which leaves the permitting authority room to require three visits anyway, and the maintenance contract must state the frequency actually used (§285.7(d)(1)(D)). Document the monitoring equipment on the contract and in the permit file before moving a system to a two-visit schedule.

What counts as an inspection or test?

The rule describes a “maintenance check and test” through three documents:

  • Figure 3, Sample Testing and Reporting Record (30 TAC §285.90(3)) lists the inspection items: aerators, filters, irrigation pumps, recirculation pumps, sludge condition, disinfection device, chlorine supply, electrical circuits, distribution system, sprayfield vegetation/seeding (if applicable), and “other as noted.” Each is marked operational or inoperative. The form also records repairs, whether access ports were secured, test results, complaint responses, and comments.
  • Table IV (30 TAC §285.91(4)) lists the tests and acceptable results shown above.
  • The tag (30 TAC §285.7(e)(2)) must be “either punched or indelibly marked with the date the system was checked at the time of each maintenance check, including any maintenance check in response to owner complaints.”

A visit that skips the component check or the required test is not a complete inspection under the rule, even if a report is filed.

Can the owner skip inspections after two years?

A single-family owner who elects to maintain the system personally under 30 TAC §285.7(d)(4) “is not subject to testing and reporting requirements” (§285.7(e)(4)). That exemption belongs to the owner, not to a contracted provider. While a maintenance contract or initial two-year service policy is in force, the full schedule applies. See Can homeowners maintain their own aerobic system in Texas?.

Can a county require more than three visits?

Yes. 30 TAC §285.3(a)(1) states that all aspects of OSSF operation and maintenance “shall be conducted according to this chapter, or according to an order, ordinance, or resolution of an authorized agent,” and TCEQ’s maintenance page notes that “Some permitting authorities have adopted more stringent requirements.” Check the county or river authority order for its inspection interval, any extra test items, and any restriction on the two-visit electronic-monitoring option. The permitting authority or TCEQ may also inspect an aerobic system at any time under §285.7(g).

Sources

Last verified: 2026-10-05. Summarizes public rules as of Oct 5, 2026; not legal advice; verify with your permitting authority.

DulyTrack tracks this for every system you service — Reserve a founding spot.

Common questions

How many times a year must a Texas aerobic septic system be inspected?

Three. 30 TAC §285.91(4), Table IV requires testing at least once every four months for surface application and secondary treatment systems, which works out to three visits per year.

Can the inspection frequency be reduced to twice a year in Texas?

Yes, under 30 TAC §285.7(e)(3), if the system has electronic monitoring and automatic telephone or radio access that notifies the provider of failures and monitors the disinfection level. The provider must keep that monitoring working.

What has to happen at each Texas aerobic inspection?

Inspect the components listed in Figure 3 (§285.90(3)), run the tests in Table IV (§285.91(4)), mark the tag (§285.7(e)(2)(D)), and report within 14 days (§285.7(e)(1)(B)).

Does a county require more frequent inspections than TCEQ?

It can. 30 TAC §285.3(a)(1) allows an authorized agent's order, ordinance, or resolution to govern, and TCEQ notes some permitting authorities have adopted more stringent requirements. Check the local order.

Sources

Summarizes the rule in plain English with the citation beside it, checked on Oct 5, 2026. Your permitting authority’s own requirements win. Not legal advice.

Filing in a particular Texas county? Each of the 254 county pages carries that county’s permitting authority, how it takes the report, and the licensed providers working there.

Find your county